Specifications of OIL MATIC
S
pecification
Specifications (series V and KTV)
Series V specifications
Inverter control method
Model
V 300 V 750 V 1500 V 2200
Effective cooling capacity
(W)
0-1600 0-4000 0-6000 0-8000
Nominal chiller capacity
(W)
300 450 700 1100
Refrigerant used R-407C
Amount of refrigerant filled
(g)
460 620 780 1380
Condenser Forced air-cooled type parallel flow type
Rated output of fan motor
(W)
25 60 150
Cooler (evaporator) Open coil
Heating exchange method Open-coil forced vortex type
Stirring motor
Rated output of motor
(W)
50 100
Power source AC200V 50/60Hz, AC220V 60Hz, 3-phase
Maximum operating current
(A)
8 9 12 20
Normal operating current
(A)
6 8 12 18
Temperature regulator Digital inverter PID controller
Setting range
Constant type (5-45°C),
follow-up type (reference temperature: -9.9°C - +9.9°C)
Range of ambient temperature 5-45 (°C)
Range of liquid temperature 5-45 (°C)
Fluid to use Coolant, water, etc.
Appearance Light gray, silver
Dimensions
(W×D×H (mm))
350×370×650
350×440×795
410×500×895
525×620×985
Weight
(kg)
40 55 70 95
* The effective cooling capacity indicates the maximum values within the range of use when oil ISO VG2 or equivalent is used.
* Specifications are subject to change without notice for improvement.
Series KTV specifications
ON-OFF control method
Model
KTV-3
KTV-5
KTV-7.5
KTV-11
KTV-15
KTV-22
KTV-38
(Note)
Effective cooling capacity
(W)
(50/60Hz)
1160/1390
1450/1740
2900/3480
3720/4460
4830/5810
7260/8720
12200/14650
Nominal chiller capacity
(W)
300 500 750 1100 1500 2200 3750
Refrigerant used R-407C
Amount of refrigerant filled
(g)
800 900 900 1450 1900 3400 4500
Condenser Forced air-cooled type cross-fin
Rated output of fan motor
(W)
25 60 60×2 85×2 85×2
Cooler (evaporator) Open coil
Heating exchange method
Open-coil forced vortex type
Stirring motor
Rated output of motor
(W)
50 100
Power source AC200V 50/60Hz, AC220V 60Hz, 3-phase
Maximum operating current
(A)
3 5 7 8 13 16 30
Normal operating current
(A)
Temperature regulator Digital setting, indicated temperature controller
Setting range
Constant type (5-45°C),
follow-up type (reference temperature: -9.9°C - +9.9°C)
Range of ambient temperature
5-45 (°C)
Range of liquid temperature 5-45 (°C)
Fluid to use Coolant, water, etc.
Appearance Light gray
Dimensions
(W×D×H (mm))
35380×950
41425×1130
47500×1260
51525×1360
54565×1460
60625×1615
73725×1970
Weight
(kg)
55 60 80 100 130 160 230
* The effective cooling capacity indicates values when oil ISO VG32 or equivalent is used at the oil temperature and an ambient
temperature of 35°C.
* Specifications are subject to change without notice for improvement.
Note: The fluid to use for the model KTV-38 is limited. For details, please contact us.